483
Troubleshooting
Section 9-2
Interrupt Task Errors
■
Reference Information
PLC Setup Errors
■
Reference Information
Option Board Errors
■
Reference Information
Battery Error
■
Reference Information
Probable cause
Possible remedy
An interrupt task error occurs when the
Detect Interrupt task errors setting in the
PLC Setup is set to
Detect and an attempt
is made to refresh a Special I/O Unit from
an interrupt task with IORF(097) while the
Unit’s I/O is being refreshed by cyclic
refreshing (duplicate refreshing).
Review the program to see whether detect-
ing interrupt task errors can be disabled or
avoided.
Error flag
Interrupt Task Error Flag, A402.13
Error code (A400)
008B
Error information
Interrupt Task Error, A426
Probable cause
Possible remedy
A set value error occurred in the PLC
Setup.
The address of the error is stored in A406
in 16-bit binary.
Correct the PLC Setup with correct val-
ues.
Error flag
PLC Setup Error Flag, A402.10
Error code (A400)
009B
Error information
PLC Setup error location, A406
Probable cause
Possible remedy
A315.13 will turn ON if the Option Board
is removed while the power is being sup-
plied.
Turn OFF the power supply and then
install the Option Board again.
Error flags
Option Board Error Flag, A315.13
Other Non-fatal Error Flag, A402.00
Error code (A400)
---
Error information
---
Probable cause
Possible remedy
If the PLC Setup is set to detect battery
errors, this error will occur when there is
an error in the battery in the CPU Unit
(i.e., the voltage is low or a battery is not
mounted).
Check the battery connections.
When using battery-free operation, dis-
able connecting battery errors in the PLC
Setup.
Error flag
Battery Error Flag, A402.04
Error code (A400)
00F7
Error information
---
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...