162
High-speed Counters
Section 5-1
5-1-3
Procedure
Select high-speed counter 0 to 3.
Select the pulse input method, reset
method, and counting range.
Select the kind of interrupt (if any).
Wire inputs.
PLC Setup settings
Ladder program
•
Pulse input methods: Differential phase (4x),
Pulse + direction, Up/Down, or Increment
•
Reset methods: Phase-Z + Software reset, Software reset,
Phase-Z + Software reset (continuing comparing),
Software reset (continuing comparing)
•
Counting ranges: Linear mode or Ring mode
•
Enable/disable interrupts
•
Target value comparison interrupt
•
Range comparison interrupt
•
Connect to the terminals (24 VDC input or line-driver)
•
High-speed Counters 0 to 3 Enable/Disable:
•
High-speed Counters 0 to 3Pulse Input Mode:
Differential phase (4x)
Pulse + direction
Up/Down
Increment
•
High-speed Counters 0 to 3 Reset Method:
Phase-Z + Software reset, Software reset, Phase-Z + Software
reset (continuing comparing), Software reset (continuing
comparing)
•
High-speed Counters 0 to 3 Counting Mode:
Linear mode
Ring mode
•
Program the interrupt task (with any interrupt number between 0
and 255) to be executed when using a target value comparison
or range comparison interrupts.
•
Register a target value comparison table and start the
comparison.
•
Register a range comparison table and start the comparison.
•
Register a target value comparison table without starting the
comparison.
•
Register a range comparison table without starting the
comparison.
•
Change the counter PV.
•
Start comparison with the registered target value comparison
table or range comparison table.
•
Read the high-speed counter PVs, read the status of the high-
speed counter comparison operation, or read the range-
comparison results.
•
Turn ON the High-speed Counter Gate Bit to stop counting input
pulses.
•
High-speed counters 0 to 3: 24 VDC input,
Response frequency: 50 kHz for single-phase, 100 kHz for
differential phase
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...