518
Auxiliary Area Allocations by Function
Appendix C
PLC Setup Error Information
I/O Information
Other PLC Operating Information
Name
Address
Description
Access
Updated
PLC Setup Error Flag
(non-fatal error)
A402.10
ON when there is a setting error in the PLC Setup.
Read-only
PLC Setup Error Location
A406
When there is a setting error in the PLC Setup, the loca-
tion of that error is written to A406 in 4-digit hexadecimal.
Read-only
Name
Address
Description
Access
Updated
Too Many I/O Points Flag
(fatal error)
A401.11
ON when the number of Expansion Units and Expansion
I/O Units exceeds the limit, when the number of words
allocated to these Units exceeds the limit, are mounted.
Read-only
Too Many I/O Points, Details A407.00 to
A407.12
Always 0000 hex.
Read-only
Too Many I/O Points, Cause
A407.13 to
A407.15
The 3-digit binary value of these bits indicates the cause
of the Too Many I/O Points Error.
010: Too many words
011: Too many Units
Read-only
I/O Bus Error Flag
(fatal error)
A401.14
ON in the following cases:
• When an error occurs in a data transfer between the
CPU Unit and a Expansion Unit or Expansion I/O Unit.
If this happens, 0A0A hex will be output to A404.
• When an error occurs in a data transfer between the
CPU Unit. If this happens, 0000 hex will be output to
A404 to indicate the first Unit, 0001 hex to indicate the
second Unit, and 0F0F hex to indicate an undeter-
mined Unit.
CPU Unit operation will stop and the ERR/ALM indicator
on the front of the CPU Unit will light.
(This flag will be turned OFF when the error is cleared.)
Read-only
I/O Bus Error Slot Number
A404
Contains information on I/O bus errors.
The CPU Unit will stop operating and the ERR/ALM indi-
cator on the front of the CPU Unit will light.
(A401.04 (I/O Bus Error Flag) will turn ON.)
(This information will be cleared when the error is
cleared.)
0A0A hex: Expansion Unit or Expansion I/O Unit error
Read-only
Duplication Error Flag
(fatal error)
A401.13
ON in the following cases:
• Two CPU Bus Units have been assigned the same unit
number.
Read-only
Unit Error Flags
A436.00 to
A436.02
ON when an error occurs in an Expansion Unit or Expan-
sion I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
CP1W/CPM1A-TS002 and CP1W/CPM1A-TS102 are
each counted as two Units.
Read-only
Number of Connected Units
A437
Stores the number of Expansion Units and Expansion
I/O Units connected as a hexadecimal number.
Note
This information is valid only when a Too Many
I/O Points error has occurred. CP1W/CPM1A-
TS002 and CP1W/CPM1A-TS102 are each
counted as two Units.
Read-only
Name
Address
Description
Access
Updated
Battery Error Flag
(non-fatal error)
A402.04
ON if the CPU Unit’s battery is disconnected or its volt-
age is low and the Detect Battery Error setting has been
set in the PLC Setup.
Read-only
Cycle Time Too Long Flag
(fatal error)
A401.08
ON if the cycle time exceeds the maximum cycle time set
in the PLC Setup (the cycle time monitoring time).
Read-only
FPD Teaching Bit
A598.00
Turn this bit ON to set the monitoring time automatically
with the teaching function.
Read/write
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...