133
1:1 Link Area
Section 4-3
■
I/O Word Allocations to Expansion Units
CPU Unit with 40 I/O TS002 + DA041 + 40ED
4-3
1:1 Link Area
The 1:1 Link Area contains 1,024 bits (64 words) with addresses ranging from
CIO 3000.00 to CIO 3063.15 (CIO 3000 to CIO 3063).
These bits are used to create 1:1 links (i.e., shared data link areas) by con-
necting the RS-232C ports of two PLCs, including the CP1L, CPM1A,
CPM2A, CPM2B, CPM2C, SRM1(-V2), CQM1H, and C200HX/HG/HE(-Z).
Refer to
6-3-6 1:1 Links
for information on using 1:1 links.
DA041
TS002
Bit
15 14 13 12 11 10
09
08 07
06 05 04 03 02
01 00
CIO 0
CIO 1
CIO 2
CIO 3
CIO 4
CIO 5
CIO 6
CIO 7
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
CIO 105
CIO 106
CIO 107
Do not use.
Can be used as work bits.
Can be used as work bits.
Do not use.
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.07
CPU Unit
(40 I/O points)
CIO 2 to CIO 5
No outputs
No inputs
CIO 2 to CIO 6.11
CIO 7 to CIO 7.11
24 input points
16 output points
24 input points
16 output points
CIO 102 to CIO 105
CIO 106.00 to CIO 106.07
CIO 107.00 to CIO 107.07
CPU Unit with 40 I/O points
First Unit: Temperature Sensor Unit
Third Unit: Expansion I/O Unit with 40
CPU Unit with 40 I/O points
Second Unit: Analog Output Unit
Third Unit: Expansion I/O Unit with 40 I/O points
First Unit:
Temperature Sensor Unit
Second Unit:
Analog Input Unit
Third Unit:
Expansion I/O Unit with 40 I/O points
Input bits
Input bits
Output bits
Output bits
RS-232C
CIO 3000
CIO 3031
CIO 3032
CIO 3063
Master
Slave
1:1 Links
CIO 3000
CIO 3031
CIO 3032
CIO 3063
Write words
Write words
Read words
Read words
CP1L,
CPM1A,
CPM2A,
CPM2B,
CPM2C,
SRM1(-V2),
CQM1H,
C200HX/HG/HE(-Z),
Other C-series PLCs
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...