232
Pulse Outputs
Section 5-2
Jog Operation
Specifications and
Operation
• Low-speed jog operation (CW) will be executed from pulse output 1 while
input 0.00 is ON.
• Low-speed jog operation (CCW) will be executed from pulse output 1
while input 0.01 is ON.
• High-speed job operation (CW) will be executed from pulse output 1 while
input 0.04 is ON.
• High-speed jog operation (CCW) will be executed from pulse output 1
while input 0.05 is ON.
Instructions Used
SPED(885) Starts and stops (immediate stop) the low-speed jog operations.
ACC(888)
Starts and stops (decelerate to a stop) the high-speed jog opera-
tions.
Preparation
■
PLC Setup
There are no settings that need to be made in the PLC Setup.
DM Area Settings
Settings to Control Speed while Jogging
(D0 to D1 and D10 to D15)
1,000 Hz
Target frequency
CW Low-speed
JOG (0.00)
CCW Low-speed
JOG (0.01)
Target frequency
100,000 Hz
CW High-speed jog
(0.04)
CCW high-speed
jog (0.05)
Acceleration/de-
celeration rate
100 Hz/4 ms
Acceleration/de-
celeration rate
100 Hz/4 ms
Setting details
Address
Data
Target frequency (low speed): 1,000 Hz
D0
03E8
D1
0000
Acceleration rate: 100 Hz/4 ms
D10
0064
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...