331
Interrupt Functions
Section 6-1
PLC Setup
Click the
Built-in Input
Tab to and set the high-speed counters that will be
used for interrupts.
Settings
Input Function Settings
According the PLC Setup
Setting
If the built-in inputs are set to be used as high-speed counters 0 to 3, the func-
tion of the input bits will change as shown in the following table. If a high-
speed counter is set to be used, the bits in CIO 0 and CIO 1 can no longer be
used for normal inputs, input interrupts, or quick-response inputs.
Item
Setting
Use high speed counter 0 to 3 Use counter
Counting mode
Linear mode
Circular mode (ring mode)
Circular Max. Count
0 to FFFF FFFF hex
(When circular (ring) mode is selected as the count-
ing mode, set maximum ring value here.)
Reset method
Phase Z and software reset
Software reset
Phase Z and software reset (continue comparing)
Software reset (continue comparing)
Input Setting
Differential phase inputs (4x)
Pulse + direction inputs
Up/Down inputs
Increment pulse input
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...