79
Computing the Cycle Time
Section 2-7
5: Peripheral Servicing
2-7-3
Functions Related to the Cycle Time
Minimum Cycle Time
Set the minimum cycle time to a non-zero value to eliminate inconsistencies in
I/O responses. A minimum cycle time can be set in the PLC Setup between 1
and 32,000 ms in 1-ms increments.
This setting is effective only when the actual cycle time is shorter than the
minimum cycle time setting. If the actual cycle time is longer than the mini-
mum cycle time setting, the actual cycle time will remain unchanged.
PLC Setup
Details
Processing time and fluctuation cause
Services USB port.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If the ports are not connected, the servicing time is 0 ms.
Services serial ports
Services communications ports.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no communications ports are used, the servicing time is 0 ms.
Services built-in flash memory access.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If there is no access, the servicing time is 0 ms.
Serves Memory Cassette access.
Minimum cycle time
(effective)
Minimum cycle time
(effective)
Minimum cycle time
(effective)
Actual cycle
time
Actual cycle
time
Actual cycle
time
Minimum cycle time
Actual cycle
time
Minimum cycle time
Actual cycle
time
Minimum cycle time (effective)
Actual cycle
time
Name
Settings
Default
Minimum cycle time
0000 to 7D00 hex
(1 to 32,000 ms in 1-ms incre-
ments)
0000 hex: Variable cycle time
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...