186
Pulse Outputs
Section 5-2
Stopping a Pulse Output
Operation
Example
application
Frequency changes
Description
Procedure
Instruction
Settings
Stop pulse
output
Immediate
stop
Stops the pulse out-
put immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
INI(880)
• Port
• Stop pulse
output
Stop pulse
output
Immediate
stop
Stops the pulse out-
put immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
SPED(885)
(Continu-
ous)
• Port
• Continuous
• Target fre-
quency=0
Stop pulse
output
smoothly
Decelerate
to a stop
Decelerates the
pulse output to a
stop.
Note
If ACC(888)
started the
operation, the
original
acceleration/
deceleration
rate will
remain in
effect.
If SPED(885)
started the
operation, the
acceleration/
deceleration
rate will be
invalid and
the pulse out-
put will stop
immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
ACC(888)
(Continu-
ous)
• Port
• Continuous
• Target fre-
quency=0
Pulse frequency
Present frequency
Execution of INI(880)
Time
Pulse frequency
Present frequency
Execution of SPED(885)
Time
Pulse frequency
Present frequency
Execution of ACC(888)
Acceleration/
deceleration rate
(Rate set at the
start of the
operation.)
Target frequency = 0
Time
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...