400
Analog Input Units
Section 7-2
Analog Input Signal
Ranges
■
−
10 to 10 V Inputs
■
0 to 10 V Inputs
■
0 to 5 V Inputs
■
1 to 5 V Inputs
Voltage in the -10 to 10 V
range corresponds to hexa-
decimal values F448 to 0BB8
(-3,000 to 3,000). The range
of data that can be converted
is F31C to 0CE4 hex (-3,300
to 3,300). A negative voltage
is expressed as two’s comple-
ment.
Voltage in the 0 to 10 V range
corresponds to hexadecimal
values 0000 to 1770 (0 to
6,000). The range of data that
can be converted is FED4 to
189C hex (-300 to 6,300). A
negative voltage is expressed
as two’s complement.
Voltage in the 0 to 5 V range
corresponds to hexadecimal
values 0000 to 1770 (0 to
6,000). The range of data that
can be converted is FED4 to
189C hex (-300 to 6,300). A
negative voltage is expressed
as two’s complement.
Voltage in the 1 to 5 V range
corresponds to hexadecimal
values 0000 to 1770 (0 to
6,000). The range of data that
can be converted is FED4 to
189C hex (-300 to 6,300).
Voltage in the range of 0.8 to
1 V is expressed as two’s
complement.
If an input is below the range
(i.e., less than 0.8 V), the
open-circuit detection func-
tion is activated and the data
becomes 8,000.
0 V
10 V 11 V
−
11 V
−
10 V
Converted data
Hexadecimal (Decimal)
0CE4 (3300)
0BB8 (3000)
0000 (0)
F448 (
−
3000)
F31C (
−
3300)
0 V
10 V 10.5 V
−
0.5 V
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (
−
300)
0 V
5 V
5.25 V
−
0.25V
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (
−
300)
1 V
5 V 5.2 V
0.8 V
Converted data
Hexadecimal (Decimal)
189c (6300)
1770 (6000)
0000 (0)
FED4 (
−
300)
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...