557
Auxiliary Area Allocations by Address
Appendix D
A406
All
PLC Setup
Error Location
When there is a setting error in the
PLC Setup, the location of that error
is written to A406 in 4-digit hexadeci-
mal.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(A406 will be cleared when the
cause of the error is eliminated.)
0000 to 01FF
hexadecimal
Cleared
Cleared
Refreshed
when error
occurs.
A402.10
A407
A407.00
to
A407.12
Too Many I/O
Points, Details
Always 0000 hex.
0000 hex
Cleared
Cleared
---
A401.11,
A407.13
to
A407.15
A407.13
to
A407.15
Too Many I/O
Points, Cause
The 3-digit binary value of these bits
indicates the cause of the Too Many
I/O Points Error.
Note
These bits will be cleared
when the error is cleared.
010: Too
many Expan-
sion Unit and
Expansion I/O
Unit words
011: Too
many Expan-
sion Units
and Expan-
sion I/O Units
Cleared
Cleared
Refreshed
when error
occurs.
---
A424
A424.00
to
A424.15
Error Option
Board Flags
The bit corresponding to the option
slot turns ON when an error occurs
in an Option Board (A315.13 will be
ON).
Bit 00: Option slot 1
Bit 01: Option slot 2
ON: Error
OFF: No error
Cleared
Cleared
---
A353.13
A436
A436.00
to
A436.02
CPM1A Unit
Error Flags
ON when an error occurs in a CP-
series Expansion Unit or Expansion
I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
OFF: No error
ON: Error
Retained
Cleared
---
---
A437
All
Number of
Connected
CPM1A Units
Stores the number of Expansion
Units and Expansion I/O Units con-
nected as a hexadecimal number.
Note
This information is valid only
when a Too Many I/O Points
error has occurred. CP1W/
CPM1A-TS002 and CP1W/
CPM1A-TS102 are each
counted as two Units.
0000 to 0007
hex
Retained
Cleared
---
---
A438
All
Pulse Output
2 Stop Error
Code
If a Pulse Output Stop Error occurs
for pulse output 2, the error code is
stored.
---
Retained
Cleared
Refreshed
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
---
A439
All
Pulse Output
3 Stop Error
Code
If a Pulse Output Stop Error occurs
for pulse output 3, the error code is
stored.
---
Retained
Cleared
Refreshed
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
---
A440
All
Max. Interrupt
Task Process-
ing Time
Contains the Maximum Interrupt
Task Processing Time in units of
0.1 ms.
(This value is written after the inter-
rupt task with the max. processing
time is executed and cleared when
PLC operation begins.)
0000 to FFFF
hexadecimal
Cleared
Cleared
See Func-
tion col-
umn.
---
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...