Power OFF Operation
Section 2-6
2.
A momentary power interruption that lasts more than 10 ms for AC power
or more than 2 ms for DC power may or may not be detected.
The following timing chart shows the CPU Unit power OFF operation in more
detail.
Power OFF Timing Chart
Description of Operation
Power OFF will be detected if the 100 to 240 V AC power supply falls below
85% of the rated voltage or the DC power supply falls below 90% of the rated
voltage for the power OFF detection time (10 ms minimum for AC power and
2 ms minimum for DC power). The CPU reset signal will turn ON while the
internal power supply is being held and the CPU Unit will be reset.
2-6-2
Instruction Execution for Power Interruptions
If power is interrupted and the interruption is detected when the CPU Unit is
operating in RUN or MONITOR mode, the instruction currently being executed
will be completed and then the CPU Unit will be reset.
10 ms
0
85% of the rated voltage or less for AC power
90% of the rated voltage or less or DC power
0 to 10 ms for AC
0 to 2 ms for DC
Momentary power
interruption not detected
and operation continues.
Greater than 10 ms for AC
Greater than 2 ms for DC
Operation will continue or stop
depending on whether or not a
momentary power interruption is
detected.
Power supply
voltage
Power supply
voltage
Time
Power OFF detection time:
The time from when the power supply voltages drops to 85% or less of the rated
voltage for AC power or 90% for DC power until the power OFF condition is detected.
Holding time for 5 V internal power supply after power OFF detection:
The maximum time that the 5 V internal power supply voltage will be maintained after
the power OFF condition is detected. The holding time is fixed at 1 ms.
AC: 85% of rated voltage
DC: 90% of rated voltage
Operation always stopped
at this point regardless.
Power OFF detected signal
Program execution status
CPU reset signal
Cyclic tasks or interrupt tasks
Stopped
Power OFF detected
Power OFF Detection
Delay Time
AC: 10 ms
DC: 2 ms
Holding time for 5 V internal
power supply after power
OFF detection: 1 ms
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...