357
Serial Communications
Section 6-3
Procedure
The Serial PLC Links operate according to the following settings in the PLC
Setup in the Polling Unit and Polled Units.
Settings at the Polling Unit
1,2,3...
1.
Set the serial communications mode of serial port 1 or 2 to Serial PLC
Links (Polling Unit).
2.
Set the link method to the Complete Link Method or Polling Unit Link Meth-
od.
3.
Set the number of link words (up to 10 words for each Unit).
4.
Set the maximum unit number in the Serial PLC Links (0 to 7).
Settings at the Polled Units
1,2,3...
1.
Set the serial communications mode of serial port 1 or 2 to Serial PLC
Links (Polled Unit).
2.
Set the unit number of the Serial PLC Link Polled Unit.
PLC Setup
Settings at the Polling Unit
Settings at the Polled Unit
Note
Both serial ports cannot be used for PLC Links at the same time. If both ports
are set for PLC Links (either as polling node or polled node), a PLC Setup set-
ting error (non-fatal error) will occur and the PLC Setup Setting Error Flag
(A402.10) will turn ON. If PLC Links is set for one serial port, set the other
serial port to a different mode.
Item
Set value
Default
Refresh timing
Serial port
1 or 2
Mode: Communications mode
PC Link (Master): PLC Link Polling Unit
Host Link
Every cycle
Baud: Baud rate
38,400 bps, 115,200 bps
9,600 bps
PC link mode: PLC Link method
ALL: Complete link method
Masters: Polling Unit method
ALL
Link words: No. of link words
1 to 10 words
10 words
PC Link Unit No.: Max. unit No.
0 to 7
0 hex
Item
Set value
Default
Refresh timing
Serial port
1 or 2
Mode: Communications mode
PC Link (Slave): PLC Link Polled Unit
Host Link
Every cycle
Baud: Baud rate
38,400 bps, 115,200 bps
9,600 bps
Unit number
0 to 7
0
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...