97
Wiring CP1L CPU Units
Section 3-4
Secure the DIN Track to the control panel using M4 screws separated by
210 mm (6 holes). The tightening torque is 1.2 N·m.
3-4
Wiring CP1L CPU Units
Note
(1) Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign mat-
ter from entering the Unit during wiring procedures.
(2) Remove the label after the completion of wiring to ensure proper heat dis-
sipation.
15
10
4.5
25
25
25
10
25
15
1000
1000 (500)
(See note.)
PFP-100N2
PFP-100N/50N
15
10
4.5
25
25
25
10
25
15 (5)
(See note.)
1
16
1.5
1
29.2
24
27
30
±
0.3
7.3
±
0.15
35
±
0.3
27
±
0.15
28.25
×
4.5 oblong holes
Note:
PFP-50N dimensions are given in parentheses.
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...