321
Interrupt Functions
Section 6-1
Input Terminal Block of
CPU Units with 30 I/O
Points
The 6 input bits CIO 0.04 to CIO 0.09 can be used for input interrupts.
Input Terminal Block of
CPU Units with 40 I/O
Points
The 6 input bits CIO 0.04 to CIO 0.09 can be used for input interrupts.
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.04 to CIO 0.09 are used as normal inputs. When using
these inputs for input interrupts, use the CX-Programmer to change the
input’s setting in the PLC Setup.
Note
*Input interrupts 4 and 5 are not supported by CPU Units with 14 I/O Points.
L1 L2/N COM
01
03
05
07
09
11
01
03
05
00
02
04
06
08
10
00
02
04
Input interrupt 0
Input interrupt 2
Input interrupt 3
Input interrupt 1
Input interrupt 5
Input interrupt 4
Inputs (CIO 0)
Inputs (CIO 1)
Upper Terminal Block
(Example: CPU Unit
with AC Power Supply)
L1
L2/N COM
01
03
05
07
09
11
01
03
05
07
09
11
00
02
04
06
08
10
00
02
04
06
08
110
Input interrupt 0
Input interrupt 2
Input interrupt 3
Input interrupt 1
Input interrupt 5
Input interrupt 4
Upper Terminal Block
(Example: CPU Unit
with AC Power Supply)
Inputs (CIO 0)
Inputs (CIO 1)
Input terminal
block
CPU Unit
Input interrupt
Task number
Word
Bit
CPU Units with
40 I/O Points
CPU Units with
30 I/O Points
CPU Units with
20 I/O Points
CPU Units with
14 I/O Points
CIO 0
00
Normal input 0
Normal input 0
Normal input 0
Normal input 0
---
---
01
Normal input 1
Normal input 1
Normal input 1
Normal input 1
---
---
02
Normal input 2
Normal input 2
Normal input 2
Normal input 2
---
---
03
Normal input 3
Normal input 3
Normal input 3
Normal input 3
---
---
04
Normal input 4
Normal input 4
Normal input 4
Normal inputs 4
Input interrupt 0
Interrupt task 140
05
Normal input 5
Normal input 5
Normal input 5
Normal inputs 5
Input interrupt 1
Interrupt task 141
06
Normal input 6
Normal input 6
Normal input 6
Normal inputs 6
Input interrupt 2
Interrupt task 142
07
Normal input 7
Normal input 7
Normal input 7
Normal inputs 7
Input interrupt 3
Interrupt task 143
08
Normal input 8
Normal input 8
Normal input 8
---
Input interrupt 4*
Interrupt task 144*
09
Normal input 9
Normal input 9
Normal input 9
---
Input interrupt 5*
Interrupt task 145*
10
Normal input 10
Normal input 10
Normal input 10
---
---
---
11
Normal input 11
Normal input 11
Normal input 11
---
---
---
CIO 1
00 to 05
Normal input 12
to 17
Normal input 12
to 17
---
---
---
---
06 to 11
Normal inputs 18
to 23
---
---
---
---
---
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...