429
Analog I/O Units
Section 7-4
Analog Output Signal
Ranges
−
10 to 10 V
The hexadecimal values F448 to 0BB8 (
−
3000 to 3000) correspond to an ana-
log voltage range of
−
10 to 10 V. The entire output range is
−
11 to 11 V. Spec-
ify a negative voltage as a two’s complement.
0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is
−
0.5 to 10.5 V. Specify a
negative voltage as a two’s complement.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
0 V
10 V
11 V
−
11 V
−
10 V
F448
(
−
3000)
F31C
(
−
3300)
0CE4
(3300)
0BB8
(3000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
0 V
10 V
10.5 V
−
0.5 V
FED4
(
−
300)
189C
(6300)
1770
(6000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
1 V
5 V
5.2 V
0.8 V
189C
(6300)
1770
(6000)
0 V
7FFF
FED4
(
−
300)
8000
Conversion Data
Hexadecimal (Decimal)
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...