![background image](http://html1.mh-extra.com/html/omron/cp1l-12-2007/cp1l-12-2007_operation-manual_742083421.webp)
388
Program Protection
Section 6-7
Write Protection
against FINS
Commands Sent to
the CPU Unit via
Networks
It is possible to prohibit write operations and other editing operations sent to
the PLC's CPU Unit as FINS commands through a network (including write
operations from CX-Programmer, CX-Protocol, CX-Process, and other appli-
cations using Fins Gateway). Read processes are not prohibited.
FINS write protection can disable write processes such as downloading the
user program, PLC Setup, or I/O memory, changing the operating mode, and
performing online editing.
It is possible to exclude selected nodes from write protection so that data can
be written from those nodes.
An event log in the CPU Unit automatically records all write processes sent
through the network and that log can be read with a FINS command.
6-7-3
Protecting Program Execution Using the Lot Number
The lot number is stored in A310 and A311 and can be used to prevent the
program from being executed on a CPU Unit with the wrong lot number.
The following instructions can be added to the program to create a fatal error
and thus prevent program execution if an attempt is made to execute the pro-
gram on a CPU Unit with the incorrect lot number. A password can also be set
to read-protect the program so that it cannot be copied, e.g., using a Memory
Cassette.
The lot number stored in A310 and A311 cannot be changed by the user.
The upper digits of the lot number are stored in A311 and the lower digits are
stored in A310, as shown below.
X, Y, and Z in the lot number are converted to 10, 11, and 12, respectively, in
A310 and A311. Some examples are given below.
Ladder Programming
Example
• The following instructions will create a fatal error to prevent the program
from being executed when the lot number is not 23905.
Lot number
A311
A310
01805
0005
0801
30Y05
0005
1130
A310
A311
Manufacturing lot
number (5 digits)
ANDL(610)
A310
#00FFFFFF
D0
FALS(007)
1
D100
<>L(306)
D0
#050923
First Cycle Flag
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...