625
PLC Setup
Appendix G
Origin Return Settings
Inverter Positioning 0
Basic Settings
Name
Default
Settings
When setting is read
by CPU Unit
Internal
address
Bits
Settings
1
Speed
0 pps
(disabled)
1 pps
At start of operation
289 and
288
00 to 15
0000 0001
hex
:
:
100,000 pps
0001 86A0
hex
000F 4240
hex
2
Acceleration Ratio
0 (disabled)
1 (pulses/4 ms)
At start of operation
290
00 to 15
0001Hex
:
:
65535
(pulses/4 ms)
FFFF hex
3
Deceleration Ratio
0 (disabled)
1 (pulses/4 ms)
At start of operation
291
00 to 15
0001 hex
:
:
65535
(pulses/4 ms)
FFFF hex
Name
Default
Settings
When setting is read
by CPU Unit
Internal
address
Bits
Settings
1
Use inverter positioning Do not use
Use
When power is turned
ON
416
00 to 03
0 hex
Do not use
1 hex
2
Gain
0: 10 (0.1 incre-
ments)
0: 10 (0.1 incre-
ments)
When power is turned
ON
418
00 to 15
0000 hex
1 (0.1 increments)
0001 hex
:
:
65,535
(0.1 increments)
FFFF hex
3
In-position range
0: 1
0: 1
When power is turned
ON
419
00 to 15
0000 hex
1
0001 hex
:
:
65,535 FFFF
hex
4
Min. output value
0: 1
0: 1
When power is turned
ON
420
00 to 15
0000 hex
1
0001 hex
:
:
65,535 FFFF
hex
5
Max. output value
0: 2,000,000
0: 2,000,000
When power is turned
ON
421, 422
00 to 15
00000000
hex
1
00000001
hex
:
:
4,294,967,295
FFFFFFFF
hex
6
Error counter overflow
detection value
0: 10,000
0: 10,000
When power is turned
ON
423
00 to 15
0000 hex
1
0001 hex
:
:
32,767
7FFF hex
7
Error counter alarm
detection value
0: 10,000
0: 10,000
When power is turned
ON
424
00 to 15
0000 hex
1
0001 hex
:
:
32,767
7FFF hex
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...