18
System Configuration
Section 1-2
CPU Units with 30 or 40 I/O Points and AC Power (CP1L-M
@@
DR-A)
When CP1W or CPM1A Expansion Units or Expansion I/O Units are con-
nected to a CPU Unit with 30 or 40 I/O Points and AC Power (CP1L-M
@@
DR-
A), it may not be possible to use the entire 300 mA from the external power
supply due to restrictions in the power supply capacity. The entire 300 mA
from the external power supply can be used if Expansion Units and Expansion
I/O Units are not connected.
Calculation Examples of Restrictions in External Power Supply Capacity
Calculate the external power supply capacity using the following calculation
example.
CPU Units with 14 or 20 I/O Points and AC Power (CP1L-L
@@
DR-A)
When CP1W or CPM1A Expansion Units or Expansion I/O Units are con-
nected to a CPU Unit with 14 or 20 I/O Points and AC Power (CP1L-L
@@
DR-
A), the external power supply cannot be used. If no Expansion Units or
Expansion I/O Units are connected, up to 200 mA can be used.
CPU Units with DC Power
CPU Units with DC power do not have an external power supply.
■
Restrictions Imposed by Ambient Temperature
There are restrictions in the power supply voltage and output load current
imposed by the ambient temperature for CPU Units with DC power. Use the
CPU Unit within the following ranges of power supply voltage and output load
current.
CPU Units with Relay Outputs (CP1L-
@@@
DR-D)
Relay Output Load Current Derating Curves for CPU Units and Expansion I/O
Units
Note
The above restrictions, apply to the relay output load current from the CPU
Unit even if Expansion I/O Units are not connected.
Item
CPU Unit
Expansion Unit
Total
Restriction
1st Unit
2nd Unit
3rd Unit
CP1L-M40DR-A
CP1W-DA041
CP1W-DA041
CP1W-DA041
5 V
0.22 A
0.08 A
0.08 A
0.08 A
0.46 A
24 V
0.08 A
0.124 A
0.124 A
0.124 A
0.452 A
Power con-
sumption
5 V
×
0.46 A = 2.3 W
24 V
×
0.452 A = 10.848 W
13.148 W
≤
18.5 W
Applicable
external power
supply capacity
18.5 W (total external power supply capacity)
−
13.148 W = 5.352 W
5.352 W/24V = 0.223 A
0.223 A
≤
0.3 A
Note
If the results exceeds 0.3 A, reduce the current consumption to 0.3 A or less.
CP1L-L14DR-D
CP1L-L20DR-D
CP1L-J14DR-D
CP1L-J20DR-D
CP1L-M30DR-D
CP1L-M40DR-D
50%
100%
55
°
C
40 45
Power voltage:
20.4 VDC
Power voltage:
21.6 VDC
0%
Ambient temperature
50%
100%
55
°
C
45
35
0%
Power voltage:
21.6 VDC
Power voltage:
20.4 VDC
Ambient temperature
50%
100%
55
°
C
45
35
0%
50
Power
voltage:
21.6 VDC
Power
voltage:
20.4 VDC
Ambient temperature
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...