Fail-safe Circuits
Section 3-1
3-1
Fail-safe Circuits
Always set up safety circuits outside of the PLC to prevent dangerous condi-
tions in the event of errors in the CP1L CPU Unit or external power supply. In
particular, be careful of the following points.
Supply Power to the
CP1L CPU Unit before
the Controlled
System
If the PLC's power supply is turned ON after the controlled system's power
supply, outputs in Units such as DC Output Units may malfunction momen-
tarily. To prevent any malfunction, add an external circuit that prevents the
power supply to the controlled system from going ON before the power supply
to the PLC itself.
Managing CPU Unit
Errors
When any of the following errors occurs, PLC operation (program execution)
will stop and all outputs from Output Units will be turned OFF.
• A CPU error (watchdog timer error) or CPU on standby
• A fatal error (memory error, I/O bus error, duplicate number error, too
many I/O points error, I/O setting error, program error, cycle time too long
error, or FALS(007) error) (See note.)
Always add any circuits necessary outside of the PLC to ensure the safety of
the system in the event of an error that stops PLC operation.
Note
When a fatal error occurs, all outputs from Output Units will be turned OFF
even if the IOM Hold Bit has been turned ON to protect the contents of I/O
memory. (When the IOM Hold Bit is ON, the outputs will retain their previous
status after the PLC has been switched from RUN/MONITOR mode to PRO-
GRAM mode.)
Managing Output
Malfunctions
It is possible for an output to remain ON due to a malfunction in the internal
circuitry of the Output Unit, such as a relay or transistor malfunction. Always
add any circuits necessary outside of the PLC to ensure the safety of the sys-
tem in the event that an output fails to go OFF.
Interlock Circuits
When the PLC controls an operation such as the clockwise and counterclock-
wise operation of a motor and if there is any possibility of an accident or
mechanical damage due to faulty PLC operation, provide an external interlock
such as the one shown below to prevent both the forward and reverse outputs
from turning ON at the same time.
Example
This circuit prevents outputs MC1 and MC2 from both being ON at the same
time even if both PLC outputs CIO 100.00 and CIO 100.01 are both ON, so
the motor is protected even if the PLC is programmed improperly or malfunc-
tions.
CP1H
MC2
CIO
100.00
MC1
CIO
100.01
MC1
MC2
Interlock circuit
Motor clockwise
Motor counterclockwise
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...