158
High-speed Counters
Section 5-1
Auxiliary Area Data
Allocation
Counter Input Modes
Differential Phase Mode
(4x)
The differential phase mode uses two phase signals (phase A and phase B)
and increments/decrements the count according to the status of these two
signals.
Conditions for Incrementing/Decrementing the Count
Pulse + Direction Mode
The pulse + direction mode uses a direction signal input and pulse signal
input. The count is incremented or decremented depending on the status (ON
or OFF) of the direction signal.
Function
High-speed counter number
0
1
2
3
PV storage words
Leftmost 4 digits
A271
A273
A317
A319
Rightmost 4 digits
A270
A272
A316
A318
Range Comparison Con-
dition Met Flags
Range 1 Comparison Condition Met Flag
A274.00
A275.00
A320.00
A321.00
Range 2 Comparison Condition Met Flag
A274.01
A275.01
A320.01
A321.01
Range 3 Comparison Condition Met Flag
A274.02
A275.02
A320.02
A321.02
Range 4 Comparison Condition Met Flag
A274.03
A275.03
A320.03
A321.03
Range 5 Comparison Condition Met Flag
A274.04
A275.04
A320.04
A321.04
Range 6 Comparison Condition Met Flag
A274.05
A275.05
A320.05
A321.05
Range 7 Comparison Condition Met Flag
A274.06
A275.06
A320.06
A321.06
Range 8 Comparison Condition Met Flag
A274.07
A275.07
A320.07
A321.07
Comparison In-progress
Flags
ON when a comparison operation is being exe-
cuted for the high-speed counter.
A274.08
A275.08
A320.08
A321.08
Overflow/Underflow Flags
ON when an overflow or underflow has
occurred in the high-speed counter’s PV.
(Used only when the counting mode is set to
Linear Mode.)
A274.09
A275.09
A320.09
A321.09
Count Direction Flags
0: Decrementing
1: Incrementing
A274.10
A275.10
A320.10
A321.10
11
12
11
10
10
9
9
8
8
8
7
7
7
6
6
6
5
5
5
4
4
4
3
3
3
2
2
2
1
1
0
Phase-A
Phase-B
Count
Phase A
Phase B
Count value
↑
L
Increment
H
↑
Increment
↓
H
Increment
L
↓
Increment
L
↑
Decrement
↑
H
Decrement
H
↓
Decrement
↓
L
Decrement
2
2
1
1
0
0
7
6
8
7
6
5
5
4
4
3
3
Pulse
Direction
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...