High-speed Counters
Section 5-1
Starting Interrupt Tasks based on Comparison Conditions
Data registered in advance in a comparison table can be compared with the
actual counter PVs during operation. The specified interrupt tasks (registered
in the table) will be started when the corresponding comparison condition is
met.
There are two comparison methods available: Target value comparison and
range comparison.
• Use the CTBL(882) instruction to register the comparison table.
• Use either the CTBL(882) instruction or INI(880) instruction to start the
comparison operation.
• Use the INI(880) instruction to stop the comparison operation.
Target Value Comparison
The specified interrupt task is executed when the high-speed counter PV
matches a target value registered in the table.
• The comparison conditions (target values and counting directions) are
registered in the comparison table along with the corresponding interrupt
task number. The specified interrupt task will be executed when the high-
speed counter PV matches the registered target value.
• Up to 48 target values (between 1 and 48) can be registered in the com-
parison table.
• A different interrupt task can be registered for each target value.
• The target value comparison is performed on all of the target values in the
table, regardless of the order in which the target values are registered.
• If the PV is changed, the changed PV will be compared with the target
values in the table, even if the PV is changed while the target value com-
parison operation is in progress.
Restrictions
A comparison condition (target value and count direction) cannot appear in
the table more than once. An error will occur if a comparison condition is
specified two or more times.
Note
When the count direction (incrementing/decrementing) changes at a PV that
matches a target value, the next target value cannot be matched in that direc-
tion.
No. 001 No. 015 No. 000
No. 020
High-speed counter PV
Comparison is
executed without
regard to the order
of the values in the
table.
Target value 1
Target value 2
Target value 3
Target value 4
Interrupt task that is started.
Time
Comparison table
Number of values = 4
Target value 1 (Incrementing)
Interrupt task = 000
Target value 2 (Incrementing)
Interrupt task = 001
Target value 3 (Decrementing)
Interrupt task = 020
Target value 4 (Incrementing)
Interrupt task = 015
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...