538
Auxiliary Area Allocations by Address
Appendix D
A218
All
Used Commu-
nications Port
Numbers
Stores the communications port
numbers used when a communica-
tions instruction is executed using
automatic communication port allo-
cations.
0000 to 0007
hex: Commu-
nications port
0 to 7
---
---
A219
A219.00
to
A219.07
Communica-
tions Port
Error Flags
ON when an error occurred during
execution of a network instruction
(SEND, RECV, CMND, or PMCR).
Bits 00 to 07 correspond to commu-
nications ports 0 to 7.
ON: Error
occurred
OFF: Normal
condition
Retained
---
---
---
A262
and
A263
All
Maximum
Cycle Time
These words contain the maximum
cycle time since the start of PLC
operation. The cycle time is recorded
in 8-digit hexadecimal with the left-
most 4 digits in A263 and the right-
most 4 digits in A262.
0 to
FFFFFFFF:
0 to
429,496,729.
5 ms
(0.1-ms units)
---
---
---
---
A264
and
A265
All
Present Cycle
Time
These words contain the present
cycle time in 8-digit hexadecimal with
the leftmost 4 digits in A265 and the
rightmost 4 digits in A264.
0 to
FFFFFFFF:
0 to
429,496,729.
5 ms
---
---
---
---
A270
to
A271
All
High-speed
Counter 0 PV
Contains the PV of high-speed
counter 0. A271 contains the left-
most 4 digits and A270 contains the
rightmost 4 digits.
The PV is cleared when operation
starts.
---
---
Cleared
Refreshed
each cycle
during
oversee
process.
Refreshed
when
PRV(881)
instruction
is exe-
cuted.
---
A272
to
A273
All
High-speed
Counter 1 PV
Contains the PV of high-speed
counter 1. A273 contains the left-
most 4 digits and A272 contains the
rightmost 4 digits.
The PV is cleared when operation
starts.
---
---
Cleared
Refreshed
each cycle
during
oversee
process.
Refreshed
when
PRV(881)
instruction
is exe-
cuted.
---
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...