460
DeviceNet I/O Link Units
Section 7-7
Note
When using Expansion Unit/Expansion I/O Unit Error Flags (A436)
in the program, set pin 4 on the DIP switch to ON. If communica-
tions are set to be cleared, the timing for clearing outputs and set-
ting the Error Flags may not agree.
(4)
LED Indicators
Used to indicate CPM1A-DRT21 status, as shown in the following table.
(5)
Expansion I/O Connecting Cable
Connected to the expansion connector of a CP1L CPU Unit or an Expan-
sion Unit or Expansion I/O Unit. The cable is included with the DeviceNet
Unit and cannot be removed.
Note
Do not touch the cables during operation. Static electricity may
cause operating errors.
(6)
Expansion Connector
Used for connecting Expansion Units or Expansion I/O Units.
Handling Unit Errors
If a communications error occurs while the slave is on standby, the appropri-
ate bit in word A436 will turn ON. The appropriate bit is determined by the
order in which the Expansion Units and Expansion I/O Units are connected.
The Unit nearest to the CPU Unit uses A436.00. Use these flags in the pro-
gram when it is necessary to detect errors.
Indicator
Color
Status
Condition
Meaning
MS
Green
Lit
Normal status
• Normal status
Flashing
Not set
• Switch settings being read
Red
Lit
Fatal error
• Fatal hardware error
(watchdog timer)
Flashing
Nonfatal error
• Incorrect switch settings.
---
OFF
Power not supplied.
• Power not supplied.
• Waiting for initialization to
start.
• Reset in progress.
NS
Green
Lit
Online and commu-
nications estab-
lished.
• Network normal and com-
munications established.
Flashing
Online and commu-
nications not estab-
lished.
• Network normal and com-
munications not estab-
lished.
Red
Lit
Fatal communica-
tions error
Unit has detected network
status preventing normal
communications.
• Node number duplications
• Bus OFF detected.
Flashing
Nonfatal communi-
cations error
• Communications timeout
or communications error
for one or more slaves.
---
OFF
Online and power
OFF.
Waiting for node number
check by master.
• Switch setting error.
• Power not supplied.
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...