184
Pulse Outputs
Section 5-2
Reset Bits
The pulse output PV will be cleared when this bit is
turned from OFF to ON.
0: Not cleared.
1: Clear PV.
A540.00
A541.00
CW Limit Input Signal Flags
This is the CW limit input signal, which is used in the
origin search.
ON when turned ON from an external
input.
A540.08
A541.08
CCW Limit Input Signal Flags
This is the CCW limit input signal, which is used in
the origin search.
ON when turned ON from an external
input.
A540.09
A541.09
Positioning completed input signals
This is the positioning completed input signal, which
is used in the origin search.
ON when turned ON from an external
input.
A540.10
A541.10
Accel/Decel Flags
ON when pulses are being output according to an
ACC(888) or PLS2(887) instruction and the output
frequency is being changed in steps (accelerating or
decelerating).
0: Constant speed
1: Accelerating or decelerating
A280.00
A281.00
Overflow/Underflow Flags
ON when an overflow or underflow has occurred in
the pulse output PV.
0: Normal
1: Overflow or underflow
A280.01
A281.01
Output Amount Set Flags
ON when the number of output pulses has been set
with the PULS instruction.
0: No setting
1: Setting made
A280.02
A281.02
Output Completed Flags
ON when the number of output pulses set with the
PULS(886)/PLS2(887) instruction has been output.
0: Output not completed.
1: Output completed.
A280.03
A281.03
Output In-progress Flags
ON when pulses are being output from the pulse
output.
0: Stopped
1: Outputting pulses.
A280.04
A281.04
No-origin Flags
ON when the origin has not been determined for the
pulse output.
0: Origin established.
1: Origin not established.
A280.05
A281.05
At-origin Flags
ON when the pulse output PV matches the origin
(0).
0: Not stopped at origin.
1: Stopped at origin.
A280.06
A281.06
Output Stopped Error Flags
ON when an error occurred while outputting pulses
in the origin search function.
0: No error
1: Stop error occurred.
A280.07
A281.07
Stop Error Codes
When a Pulse Output Stop Error occurs, the error
code is stored in that pulse outputs corresponding
Stop Error Code word.
---
A444
A445
Function
Pulse output number
0
1
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...