440
Temperature Sensor Units
Section 7-5
DIP Switch Settings
The DIP switch is used to set the temperature unit (
°
C or
°
F) and the number
of decimal places used.
Note
For details on 2-decimal-place Mode, refer to
Two-decimal-place Mode
on
page 447.
Rotary Switch Setting
!Caution
Set the temperature range according to the type of temperature sensor con-
nected to the Unit. Temperature data will not be converted correctly if the tem-
perature range does not match the sensor.
!Caution
Do not set the temperature range to any values other than those for which
temperature ranges are given in the following table. An incorrect setting may
cause operating errors.
The rotary switch is used to set the temperature range.
SW1
Setting
1
Temperature unit
OFF
°
C
ON
°
F
2
Number of decimal
places used (See note.)
(0.01 expression)
OFF
Normal (0 or 1 digit after the decimal
point, depending on the input range)
ON
2-decimal-place Mode
Temperature input terminals
DIP Switch
Used to set the temperature
unit and the number of
decimal places used.
Rotary Switch
Used to set the
temperature input range.
ON
1
2
Setting
CP1W-TS001/TS002
CPM1A-TS001/002
CP1W-TS101/TS102
CPM1A-TS101/102
Input type
Range (
°
C)
Range (
°
F)
Input type
Range (
°
C)
Range (
°
F)
0
K
−
200 to 1,300
−
300 to 2,300
Pt100
−
200.0 to 650.0
−
300.0 to
1,200.0
1
0.0 to 500.0
0.0 to 900.0
JPt100
−
200.0 to 650.0
−
300.0 to
1,200.0
2
J
−
100 to 850
−
100 to 1,500
---
Cannot be set.
3
0.0 to 400.0
0.0 to 750.0
---
4 to F
---
Cannot be set.
---
Summary of Contents for CP1L - 12-2007
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv TABLE OF CONTENTS...
Page 21: ...xxii...
Page 33: ...xxxiv Conformance to EC Directives 6...
Page 65: ...32 Function Blocks Section 1 5...
Page 428: ...395 Clock Section 6 9...
Page 429: ...396 Clock Section 6 9...
Page 523: ...488 Troubleshooting Unit Errors Section 9 4...
Page 531: ...496 Replacing User serviceable Parts Section 10 2...
Page 563: ...528 Auxiliary Area Allocations by Function Appendix C...
Page 611: ...576 Auxiliary Area Allocations by Address Appendix D...
Page 638: ...603 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 639: ...604 Connections to Serial Communications Option Boards Appendix F...
Page 669: ...634 Index...
Page 671: ...636 Revision History...