8. Maintenance Functions
8.2 Data Sampling
III
-72
8.2.4 Data Output Procedures
The sampled data can be output by setting "S" in "# ( )" on the DATA OUT screen.
[DATA OUT]
IN/OUT
2
<LOCK>
# 1 MAIN PROGRAM
# 2 TOOL DATA
OFF
#11 PORT NO.
2
# 3 PARAMETER
OFF
#12 DEVICE NO.
1
# 5 COMMON VARI.
OFF
(FDD:9600bps)
#30 MACRO PROGRAM
#28 AUX-PARA.
#60 TRACE DATA
#99
MAINTENANCE
<OUTPUT DATA>
#( S) DATA( ) (
)
INPUT
OUTPUT
ERASE FILE MENU
(Note 1)
The data will not be output if sampling has not been executed.
(Note 2)
The data will not be output if the sampling output valid parameter is not set to valid.
(Sampling output is validated by setting setup parameter "#1224 aux08/bit0" to 1.)
(Note 3)
Sampling data cannot be output during sampling execution.
The output data is the sampling buffer dumped with a long data length (4 bytes).
The header, etc., are not added, and the sampling data is output immediately.
(Example)
When number of sampling points is "2" ("2" MARKS" = 2)
00044363
000222A8
00044363
000222A8
00044363
:
... 1st point 1st scan data
... 2nd point 1st scan data
... 1st point 2nd scan data
... 2nd point 2nd scan data
... 1st point 3rd scan data
: