CHAPTER 13 RS-485 COMMUNICATIONS
Modbus RTU Communications
13-3
13
Set existence and logic of a parity and a stop bit length.
Characters are organized for each setting as follows:
LSB
MSB
PA2_93
0 1 2 3 4 5 6 7 8 9 10 11
0, 1
Start
Data (8 bits)
Parity Stop
2 Start
Data
(8
bits)
Stop
3, 4
Start
Data (8 bits)
Parity Stop (2 bits)
5
Start
Data (8 bits)
Stop (2 bits)
(4) Response time and communication time over
No.
Parameter name
Setting range
Default
value
Change
PA2_94
Response time
0.00 to 1.00 [s] (*)
0.00
Always
PA2_95 Communication
time over
0.00 [s]: No detection
0.01 to 9.99 [s]
0.00 Always
(*) Actual response time is set to PA2_94 setting or {time for 3 char amplifier’s processing time},
whichever is longer.
Set the response time and communication time over parameters if needed.
For details, refer to pages 13-34 (response time) and 13-35 (communication time over).
Summary of Contents for ALPHA5 Smart
Page 1: ...24C7 E 0016c FUJI SERVO SYSTEM ALPHA5 Smart USER S MANUAL...
Page 2: ......
Page 4: ...ii...
Page 36: ...CHAPTER 0 INTRODUCTION 0 16 Combination between Servomotor and Servo Amplifier 0...
Page 276: ...CHAPTER 4 PARAMETER 4 108 Output Terminal Function Setting Parameter 4...
Page 368: ...CHAPTER 6 KEYPAD 6 56 Test Operation Mode 6...
Page 392: ...CHAPTER 7 MAINTENANCE AND INSPECTION 7 24 Troubleshooting 7...
Page 472: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 488: ...CHAPTER 12 POSITIONING DATA 12 16 Response Time 12...
Page 592: ...CHAPTER 14 PC LOADER 14 48 Parameter Conversion Tool 14 1 2 3 4 6 7 8 9 10 11...
Page 633: ...CHAPTER 15 APPENDIXES Product Warranty 15 41 15 15 9 Product Warranty...
Page 634: ...CHAPTER 15 APPENDIXES 15 42 Service Network 15 15 10 Service Network...
Page 635: ......