CHAPTER 3 OPERATION
Operation
3-9
3
(2) Position control setting
The factory shipment settings of the VV type servo amplifier are as follows.
Assignment of input terminal (CONT input signal)
CONT1: Servo-on [S-ON] (Function No. 1)
CONT2: Alarm reset [RST] (Function No. 11)
CONT3 to CONT24: (No designation)
Parameter PA1_01: Control mode selection = 0 (position control)
Therefore the power-on state is the position control mode.
CONT1: Turn on servo-on [S-ON] and supply a pulse to turn the motor.
(3) Confirmation of position control
Confirm the position control mode. The third character "P" from the left indicates position control.
(4) Confirmation of pulse amount
Issue a pulse from the host controller. Check that the count agrees with that of the servo amplifier.
The display example for 100000000-pulse is shown.
With A/B phase pulse, four times the pulse count is displayed.
SET
(1 sec. or over)
ESC
Sn01
TpoF
SHIFT
SET
(1 sec. or over)
ESC
on12
01
0000
SHIFT
0000
Summary of Contents for ALPHA5 Smart
Page 1: ...24C7 E 0016c FUJI SERVO SYSTEM ALPHA5 Smart USER S MANUAL...
Page 2: ......
Page 4: ...ii...
Page 36: ...CHAPTER 0 INTRODUCTION 0 16 Combination between Servomotor and Servo Amplifier 0...
Page 276: ...CHAPTER 4 PARAMETER 4 108 Output Terminal Function Setting Parameter 4...
Page 368: ...CHAPTER 6 KEYPAD 6 56 Test Operation Mode 6...
Page 392: ...CHAPTER 7 MAINTENANCE AND INSPECTION 7 24 Troubleshooting 7...
Page 472: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 488: ...CHAPTER 12 POSITIONING DATA 12 16 Response Time 12...
Page 592: ...CHAPTER 14 PC LOADER 14 48 Parameter Conversion Tool 14 1 2 3 4 6 7 8 9 10 11...
Page 633: ...CHAPTER 15 APPENDIXES Product Warranty 15 41 15 15 9 Product Warranty...
Page 634: ...CHAPTER 15 APPENDIXES 15 42 Service Network 15 15 10 Service Network...
Page 635: ......