CHAPTER 4 PARAMETER
Basic Parameters
4-7
4
PA1_02 INC/ABS system selection
No. Name
Setting
range
Default
value
Change
02
INC/ABS selection 0: Incremental system 1: Absolute system
2: Non-overflow absolute system (not detect the
multi-turn overflow)
0 Power
Select either the relative position (incremental) system or absolute position system.
Reference
value
Function Description
0
Relative position
(incremental) system
The current position is lost after the power is turned off.
Homing must be performed again.
1
Absolute position
system
The current position is stored in memory even after the
power is turned off. Homing is unnecessary. You can
operate in the limited range. If the operation range is
exceeded, an alarm and stoppage are caused.
(Operation range: between -32767 and +32766 revolutions
of motor shaft)
2
Non-overflow absolute
system
(not detect the
multi-turn overflow)
The current position is stored in memory even after the
power is turned off. Homing is unnecessary.
Because there is no limit in the operation range, this
system is best for the control of the rotating body. (The
multi-turn data over flow alarm is not detected.)
Multi-rotation data should be processed at the host
controller suitably.
Specify so that the ratio of PA1_06 to 07 = 2
n
/1.
To establish an absolute position system, set this parameter at "1" or "2." In addition, install the
optional absolute backup battery.
Because a multi-turn data over flow alarm (dL1 alarm) is detected when the power is turned on,
perform position presetting to remove the alarm and start operation.
To use in an absolute position system, refer to "CHAPTER 11 ABSOLUTE POSITION
SYSTEM."
Notes for setting the endless absolute system
<Notes regarding settings>
1) Set the electronic gear so that it obtains: PA1_06/07 = 2 n (n
≥
2)
The absolute system encode works as a 34-bit ring counter consisting of 18-bit single-turn
counter and 16-bit multi-turn counter. On the other hand, as the current position output to the
host device via Modbus-RTU is given a 32-bit data, the size must be matched each other using
the electronic gear setting.
2) Set the parameter PA2_25 (position command format) to "0" (normal PTP).
If set to "1" (endless), current position is reset (but the multi-turn data of the encoder is not
cleared) every time the positioning operation (positioning data operation and immediate value
operation) is started. Therefore, it will be difficult to recognize the current positions from the
host device.
<Notes regarding functions>
1) The following functions are disabled: hardware OT, software OT and limiter detection.
Summary of Contents for ALPHA5 Smart
Page 1: ...24C7 E 0016c FUJI SERVO SYSTEM ALPHA5 Smart USER S MANUAL...
Page 2: ......
Page 4: ...ii...
Page 36: ...CHAPTER 0 INTRODUCTION 0 16 Combination between Servomotor and Servo Amplifier 0...
Page 276: ...CHAPTER 4 PARAMETER 4 108 Output Terminal Function Setting Parameter 4...
Page 368: ...CHAPTER 6 KEYPAD 6 56 Test Operation Mode 6...
Page 392: ...CHAPTER 7 MAINTENANCE AND INSPECTION 7 24 Troubleshooting 7...
Page 472: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Page 488: ...CHAPTER 12 POSITIONING DATA 12 16 Response Time 12...
Page 592: ...CHAPTER 14 PC LOADER 14 48 Parameter Conversion Tool 14 1 2 3 4 6 7 8 9 10 11...
Page 633: ...CHAPTER 15 APPENDIXES Product Warranty 15 41 15 15 9 Product Warranty...
Page 634: ...CHAPTER 15 APPENDIXES 15 42 Service Network 15 15 10 Service Network...
Page 635: ......