V3.5 14/08/19
UD0089
Page 101
This Document is uncontrolled unless over stamped "CONTROLLED DOCUMENT"
Recipient 1 ():
9.
Type the Trigger 1, Serial Sequence followed by Enter.
Serial Sequence (00,00):
69
,
<Alarm_Code>
This must be entered in the following format. Type 69, followed by an alarm code. For example, to send an e-
mail if when alarm code 6 (iFob Forced From System) occurs type 69,06.
NOTE:
Two digits must be entered for the alarm code. For example enter 69,06 and not 69,6.
section for a full list of alarm codes and descriptions.
10.
For the next three settings please keep the default settings as shown below. If you do not want to change a
value, just press Enter to skip.
CP1 [A/I/X] (X):
CP2 [A/I/X] (X):
CP3 [A/I/X] (X):
11.
Type the Trigger 1, Message followed by Enter. This would typically be the description of the alarm code.
For example, if you wish to send an e-mail for alarm code 6, enter the description 'iFob Forced From System'.
Message ():
iFob Forced From System
12.
Enter the Trigger 1, Priority level followed by Enter. Enter H for high priority or L for low priority.
Priority (L):
L
13.
For the next two settings please keep the default settings as shown below. If you do not want to change a
value, just press Enter to skip.
Minimal notification interval (0 s):
Re-notification interval (0 s):
14.
Repeat steps 7 to 11 for Trigger 2 and Trigger 3.
15.
When you are happy with the configuration, type 9 (Save and exit) followed by Enter.
16.
The device will automatically re-boot ready for use with the new settings. This will take approximately 10 to
20 seconds.