TIMEOUT MODE
Selects which Modbus/TCP register accesses
reset the timeout counter.
2
=
Control
RW
ACS355:
FB PAR 21
ACSM1:
FBA PAR21
ACS850/ACQ810:
FBA par21
ACS880/ACS580:
Timeout mode
0
= None
The Modbus/TCP timeout feature is disabled.
1
= Any message
The timeout counter is reset when any Modbus
register of the drive is accessed.
2
= Control RW
The timeout counter is reset when the drive
receives either a new Control word or new
reference value (REF1 or REF2) from the
Modbus/TCP client.
22
WORD ORDER
Selects in which order the 16-bit registers of
32-bit parameters are transferred.
For each register (16-bit), the first byte contains
the high order byte and the second byte
contains the low order byte.
1
= HILO
ACS355:
FB PAR 22
ACSM1:
FBA PAR22
ACS850/ACQ810:
FBA par22
ACS880/ACS580:
Word order
0
= LOHI
The first register contains the low order word
and the second register contains the high order
word.
1
= HILO
The first register contains the high order word
and the second register contains the low order
word.
23
…
26
Reserved
These parameters are not used by the adapter
module when the module is configured for
Modbus/TCP.
N/A
No.
Name/Value
Description
Default
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...