336 PROFINET IO – Communication protocol
The table below shows the PROFIdrive parameter request error
codes
.
Error #
Meaning
Used at
00h
Impermissible
parameter number
Access to an unavailable parameter
01h
Parameter value cannot
be changed
Change access to a parameter value
that cannot be changed
02h
Low or high limit
exceeded
Change access with a value outside
the limits
03h
Invalid subindex
Access to an unavailable subindex
04h
No array
Access with a subindex to a non-
indexed parameter
05h
Incorrect data type
Change access with a value that
does not match the data type of the
parameter
06h
Setting not permitted
(can only be reset)
Change access with a value unequal
to 0 when this is not permitted
07h
Description element
cannot be changed
Change access to a description
element that cannot be changed
09h
No description data
available
Access to an unavailable description
(parameter value is available)
0Bh
No operation priority
Change access rights without rights
to change parameters
0Fh
No text array available
Access to a text array that is not
available (Parameter value is
available.)
11h
Request cannot be
executed because of
operating mode
Access is temporarily not possible
for reasons that are not specified in
detail.
14h
Value impermissible
Change access with a value that is
within limits but is not permissible for
other long-term reasons (parameter
with defined single values)
15h
Response too long
The length of the current response
exceeds the maximum transmittable
length.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...