354 PROFINET IO – Communication protocol
Fault buffer mechanism
The PROFIdrive profile has a mechanism that can store eight fault
situations to PROFIdrive parameters. Fault and diagnostic data,
like fault number and fault code, can be accessed simultaneously
with only one subindex. The mechanism consists of four
PROFIdrive parameters:
•
PNU944: Fault message counter.
•
Incremented each time the fault buffer changes.
•
PNU945: PROFIdrive fault codes presented in section
Fault
code mapping
on page
352
.
•
PNU946: Fault code list that converts fault numbers to fault
codes.
•
Read using the fault number as a subindex to get the
corresponding fault code.
•
PNU947: Fault numbers according to the DRIVECOM profile.
0x900F
External
9000, 9001, 9081,
FF81, FF82, FF8E,
FF90
0x9010
Technology
6382
0x9011
Engineering
0x9012
Other
5080, 5093, 5210,
5300, 6200, 7583,
8110, 8500, 8582,
8583, FF61, FF69,
FF6A, FF83, FF84,
FF95
ChannelErrorType
Description
DRIVECOM fault
numbers
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...