272 PROFINET IO – Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal) –> READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal) –> OPERATING (Speed mode).
Position control using the PROFIdrive communication
profile with PPO Type 4
This example shows how to configure a basic positioning
application. The start/stop commands and reference are according
to the PROFIdrive profile, positioning mode. For more information,
see the PROFIdrive state machine on page
313
.
Note:
By default, fieldbus is not the only control source. See actual
signal 02.12 FBA MAIN CW in
ACSM1 Motion Control Program
Firmware Manual
for details.
The position set point and velocity reference are defined as 32-bit
integer values; both are scaled as defined in the drive parameter
settings.
The table below gives the recommended drive parameter settings.
Direction
PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
Out
Control word
(STW1)
Position set point
Velocity reference
N/A
In
Status word
(ZSW1)
Position actual
value
Velocity actual value
N/A
Drive parameter
Setting for ACSM1
drives
Description
50.01 FBA ENABLE
Enable
Enables communication between
the drive and the fieldbus adapter
module.
50.02 COMM LOSS
FUNC
Fault
Enables fieldbus communication
fault monitoring.
50.03 COMM LOSS T
OUT
3.0 s
Defines the fieldbus communication
break supervision time.
50.04 FBA REF1
MODESEL
Position
Selects the fieldbus reference 1
scaling.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...