Modbus/TCP – Start-up 73
7. Define the process data transferred to and from the drive in
parameter groups 52 and 53.
Note:
The adapter module assigns the Control word, Status
word, references 1…2 and actual values 1…2 automatically to
Modbus registers. Process data groups are not available in the
ABB Drives - Classic communication profile.
8. Validate the settings made in parameter groups 51, 52 and 53
with parameter 51.27 FBA par refresh.
9. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACS850 and ACQ810
Speed control using the ABB Drives – Enhanced
communication profile
This example shows how to configure a speed control application
that uses the ABB Drives - Enhanced profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
ABB Drives
communication profile
on page
87
.
When Reference 1 (REF1) is used, a reference value of ±20000
(4E20h) corresponds to the reference set with parameter 19.01
Speed scaling in the forward and reverse directions.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...