64 Modbus/TCP – Start-up
Parameter setting examples – ACS355
Speed and torque control using the ABB Drives –
Enhanced communication profile
This example shows how to configure a speed and torque control
application that uses the ABB Drives - Enhanced profile. In
addition, some application-specific data is added to the
communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
ABB Drives
communication profile
on page
87
.
When Reference 1 (REF1) is used, a reference value of ±20000
(decimal) corresponds to the reference set with parameter 1105
REF1 MAX in the forward and reverse directions.
When Reference 2 (REF2) is used, a reference value of ±10000
(decimal) corresponds to the reference set with parameter 1108
REF2 MAX in the forward and reverse directions.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
The table below gives the recommended drive parameter settings.
Output data
Modbus
register
Input data
Modbus
register
Control word
(4)00001
Status word
(4)00051
Speed reference
(4)00002
Speed actual value
(4)00052
Torque reference
(4)00003
Torque actual value
(4)00053
Constant speed 1
1)
(4)00004
Power
1)
(4)00054
Constant speed 2
1)
(4)00005
DC bus voltage
1)
(4)00055
1)
Example
Drive parameter
Setting for ACS355
drives
Description
9802 COMM PROT SEL
4
= EXT FBA
Enables communication
between the drive and the
fieldbus adapter module.
5101 FBA TYPE
ETHERNET
1)
Displays the type of the fieldbus
adapter module.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...