![background image](http://html.mh-extra.com/html/abb/fena-01/fena-01_user-manual_186223.webp)
EtherNet/IP – Communication protocol 223
Instance attributes (Instance
#1)
#
Attribute
name
Services
Description
Data
type
3
Run 1
Get, Set
0 = Stop, 1 = Run.
See the Run/Stop event matrix
on page
162
.
BOOL
4
Run 2
Get, Set
0 = Stop, 1 = Run.
See the Run/Stop event matrix
on page
162
.
BOOL
5
Net Control
Get, Set
0 = Local Control, 1 = Network
Control
BOOL
6
State
Get
State of Object.
See section
State (Control
supervisor object)
on page
167
.
UINT8
7
Running 1
Get
0 = Stopped, 1 = Running
BOOL
8
Running 2
Get
0 = Stopped, 1 = Running
BOOL
9
Ready
Get
1 = Ready, Enabled or
Stopping; 0 = Other state
BOOL
10
Faulted
Get
0 = Not faulted, 1 = Fault
occurred
BOOL
11
Warning
Get
0 = No Warnings present, 1 =
Warning
BOOL
12
FaultRst
Get, Set
0
→
1 Fault Reset
BOOL
13
Fault Code
Get
The fault that caused the last
transition to the Faulted state.
DRIVECOMM codes are
reported. See the drive
manual for further information
on DRIVECOMM codes.
UINT16
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...