156 EtherNet/IP – Start-up
5. Enter the following information.
The example below uses ODVA AC/DC assembly instances
121 and 171. The PLC will transmit and receive 12 words.
Type a name for the
adapter module.
Type the Input and Output
Assembly Instance
numbers.
Select the sizes of the
Input and Output words for
the adapter module.
FENA uses 16-bit words.
Change
Comm Format
to
Data - INT
(16 bits).
Type the IP address of the
adapter module.
Set
Configuration
as 1
and
Size
as 0.