162 EtherNet/IP – Communication profiles
ODVA output attributes
This section briefly describes the instances found in the output
assemblies of the ODVA AC/DC drive profile. Note that all output
assembly instances do not support all attributes listed here.
Run Forward & Run Reverse (Control supervisor object)
These attributes are used to assert run and stop commands to the
Control supervisor object state machine according to the following
Run/Stop event matrix. See
State (Control supervisor object)
on
page
167
.
Fault Reset (Control supervisor object)
This attribute resets a drive fault on a transition from zero to one if
the condition that caused the fault has been cleared.
Net Ctrl (Control supervisor object)
This attribute requests that the drive Run/Stop command be
supplied locally (Net Ctrl = 0) or by the network (Net Ctrl = 1).
Net Ref (AC/DC drive object)
This attribute requests that the drive speed and torque references
be supplied locally (Net Ref = 0) or by the network (Net Ref = 1).
RunFwd
RunRev
Trigger event
Run type
0
0
Stop
N/A
0
→
1
0
Run
RunFwd
0
0
→
1
Run
RunRev
0
→
1
0
→
1
No Action
N/A
1
1
No Action
N/A
0
→
1
1
Run
RunRev
1
1
→
0
Run
RunFwd
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...