Modbus/TCP – Start-up 77
5. Select application-specific values for the rest of the parameters
in group 50, starting from 50.04.
Examples of appropriate values are shown in the tables below.
6. Set the module configuration parameters in group 51.
•
Select the communication protocol and profile with
parameter 51.02 and configure the network settings with
parameters 51.03…51.13.
•
With parameters 51.20 and 51.21, select how the adapter
module detects fieldbus communication breaks.
7. Define the process data transferred to and from the drive in
parameter groups 52 and 53.
Note:
The adapter module assigns the Control word, Status
word, references 1…2 and actual values 1…2 automatically to
Modbus registers. Process data groups are not available in the
ABB Drives - Classic communication profile.
8. Save the valid parameter values to permanent memory with
parameter 96.07 Parameter save manually.
9. Validate the settings made in parameter groups 51, 52 and 53
with parameter 51.27 FBA A par refresh.
10. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...