![background image](http://html.mh-extra.com/html/abb/fena-01/fena-01_user-manual_186271.webp)
PROFINET IO – Start-up 271
51.01 FBA TYPE
ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 FBA PAR2
(PROTOCOL/PROFILE)
10
(= PNIO Pdrive)
Selects the PROFINET IO
protocol and PROFIdrive
profile.
51.03 FBA PAR3
(COMMRATE)
0
(= Auto)
2
)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 FBA PAR4
(IP CONFIGURATION)
0
(= Static IP)
Configuration will be obtained
from parameters
05
…
13
or
from the PLC via the DCP
protocol.
52.01 FBA DATA IN1
4
(= SW 16bit)
1)
Status word
52.02 FBA DATA IN2
5
(= Act1 16bit)
Actual value 1 (speed)
52.03 FBA DATA IN3
122
2)
Power
52.05 FBA DATA IN5
107
2)
DC bus voltage
53.01 FBA DATA OUT1
1
(= CW 16bit)
1)
Control word
53.02 FBA DATA OUT2
2
(= Ref1 16bit)
Reference 1 (speed)
53.03 FBA DATA OUT3
2408
2)
Constant speed
53.05 FBA DATA OUT5
2410
2)
Speed reference for jogging
function 1
51.27 FBA PAR REFRESH
REFRESH
Validates the FENA-11/-21
configuration parameter
settings.
10.01 EXT1 START FUNC
FBA
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
24.01 SPEED REF1 SEL
FBA REF1
Selects the fieldbus reference 1
as the source for speed
reference 1.
34.03 EXT1 CTRL MODE1
Speed
Selects speed control as the
control mode 1 for external
control location 1.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter
Setting for ACSM1
drives
Description
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...