Modbus/TCP – Communication protocol 99
ABB Drives profile - Classic
The ABB Drives profile - Classic communication profile provides
register mapped access to the control, status, reference and actual
values of the ABB Drives profile in the classic format for backward
compatibility.
Register Address
1)
Register Data (16-bit)
(4)00001
ABB Drives Profile Control
(4)00002
ABB Drives Profile Reference 1
(4)00003
ABB Drives Profile Reference 2
(4)00004
ABB Drives Profile Status
(4)00005
ABB Drive Profile Actual 1
(4)00006
ABB Drive Profile Actual 2
(4)00101…(4)09999
Drive Parameter Access (16-bit)
Register Address = (4)00000 + 100 × Group +
Index
Example for Drive Parameter 3.18:
(4)00000 + 100 × 3 + 18 = 400318
(4)20000…(4)29999
Drive Parameter Access (32-bit)
(not supported with ACS355):
Register Address = (4)20000 + 200 × Group +
2 × Index
Example for Drive Parameter 1.27:
(4)20000 + 200 × 1 + 2 × 27 = 420254
1)
6-digit register addressing ([4]00001) is used instead of 5-digit register
addressing ([4]0001) to describe the register map. See section
Register
addressing
on page
96
for additional information.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...