EtherNet/IP – Communication protocol 227
Fieldbus configuration object, class 91h
The fieldbus configuration object allows you to configure the
fieldbus configuration groups without the need to know the drive-
specific groups associated with the configuration groups.
Note:
When you use the fieldbus configuration object to update the
fieldbus configuration groups, changes to the fieldbus configuration
will only take effect when a reset service is requested of the
Identity Object, the module is powered up the next time or when a
‘Fieldbus Adapter parameter refresh’ is given.
Class attributes
Instance #1: FENA-01/-11/-21 configuration parameters
group A (group 1)
The actual parameter group number depends on the drive type.
Group A (group 1) corresponds to:
•
parameter group 51 in ACS355, ACSM1, ACS850 and
ACQ810
•
parameter group 51 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 54 if the adapter is
installed as fieldbus adapter B.
#
Attribute
name
Services
Description
Data
type
1
Revision
Get
Revision of the Configuration
Object
Array of
UINT8
#
Attribute name
Services Description
Data
type
1
Configuration Group
A (Group 1) -
Parameter 1
Get, Set
See
01
FBA TYPE
on
page
117
.
UINT16
2
Configuration Group
A (Group 1) -
Parameter 2
Get, Set
See
02
PROTOCOL/
PROFILE
on page
117
.
UINT16
3
Configuration Group
A (Group 1) -
Parameter 3
Get, Set
See
03
COMM RATE
on page
118
.
UINT16
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...