EtherNet/IP – Start-up 135
5103 FB PAR 3
(COMMRATE)
0
(= Auto)
2)
Ethernet communication rate is
negotiated automatically by the
device.
5104 FB PAR 4
(IP CONFIGURATION)
0
(= Static IP)
2)
Configuration will be obtained from
parameters
05
...
13
.
5105 FB PAR 5
(IP ADDRESS 1)
192
2)
First part of the IP address
5106 FB PAR 6
(IP ADDRESS 2)
168
2)
Second part of the IP address
5107 FB PAR 7
(IP ADDRESS 3)
0
2)
Third part of the IP address
5108 FB PAR 8
(IP ADDRESS 4)
16
2)
Last part of the IP address
5123 FB PAR 23
(ODVA SPEED SCALE)
128
2)
Sets the scaling for the ODVA
speed reference.
3018 COMM FAULT
FUNC
1
= FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT
TIME
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
5401 FBA DATA IN 1
106
2)
Power
5402 FBA DATA IN 2
107
2)
DC bus voltage
5501 FBA DATA OUT 1
1202
2)
Constant speed 1
5502 FBA DATA OUT 2
1203
2)
Constant speed 2
5127 FBA PAR
REFRESH
1
= REFRESH
Validates the FENA-01/-11/-21
configuration parameter settings.
9904 MOTOR CTRL
MODE
1
= VECTOR: SPEED Selects the speed control mode as
the motor control mode.
1001 EXT1
COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus reference 1 as
the source for speed reference 1.
Drive parameter
Setting for ACS355
drives
Description
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...