PROFINET IO – Start-up 285
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for ACS880
drives
Description
50.01 FBA A enable
1
= Option slot 1
2)
Enables communication between
the drive and the fieldbus adapter
module.
50.04 FBA A ref1 type
4
= Speed
Selects the fieldbus A reference 1
type and scaling.
50.07 FBA A act1 type
0
= Auto
Selects the actual value type and
scaling according to the currently
active Ref1 mode defined in
parameter 50.04.
51.01 FBA A type
128
= ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 Protocol/Profile
10
= PNIO Pdrive
Selects the PROFINET IO
protocol and the PROFIdrive
profile.
51.03 Commrate
0
= Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 IP configuration
0
= Static IP
Configuration will be obtained
from parameters
05
…
13
or from
the PLC via the DCP protocol.
52.01 FBA data in1
4
= SW 16bit
1)
Status word
52.02 FBA data in2
5
= Act1 16bit
Actual value 1
52.03 FBA data in3
01.14
Output power
52.05 FBA data in5
01.11
DC voltage
53.01 FBA data out1
1
= CW 16bit
1)
Control word
53.02 FBA data out2
2
= Ref1 16bit
Reference 1 (speed)
53.03 FBA data out3
22.26
Constant speed 1
53.05 FBA data out5
22.27
Constant speed 2
51.27 FBA A par refresh
1
= Refresh
Validates the FENA-11/-21
configuration parameter settings.
19.12 Ext1 control mode
2
= Speed
Selects speed control as the
control mode 1 for external control
location 1.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...