![background image](http://html.mh-extra.com/html/abb/fena-01/fena-01_user-manual_186139.webp)
EtherNet/IP – Start-up 139
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for ACSM1
drives
Description
50.01 FBA ENABLE
Enable
Enables communication between
the drive and the fieldbus adapter
module.
50.02 COMM LOSS
FUNC
Fault
2)
Enables fieldbus communication
fault monitoring.
50.03 COMM LOSS T
OUT
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
50.04 FBA REF1
MODESEL
Speed
Selects the fieldbus reference 1
scaling.
51.01 FBA TYPE
ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 FBA PAR2
(PROTOCOL/PROFILE)
100
(= EIP AC/DC)
Selects the EtherNet/IP protocol
and the ODVA AC/DC drive
profile.
51.03 FBA PAR3
(COMMRATE)
0
(= Auto
2
)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 FBA PAR4
(IP CONFIGURATION)
0
(= Static IP)
2)
Configuration will be obtained
from parameters
05
…
13
.
51.05 FBA PAR5
(IP ADDRESS 1)
192
2)
First part of the IP address
51.06 FBA PAR6
(IP ADDRESS 2)
168
2)
Second part of the IP address
51.07 FBA PAR7
(IP ADDRESS 3)
0
2)
Third part of the IP address
51.08 FBA PAR8
(IP ADDRESS 4)
16
2)
Last part of the IP address
51.09 FBA PAR9
(SUBNET CIDR)
24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
51.23 FBA PAR23
(ODVA SPEED SCALE)
128
2)
Sets the scaling for the ODVA
speed reference.
52.01 FBA DATA IN1
122
2)
Power
52.03 FBA DATA IN3
107
2)
DC bus voltage
53.01 FBA DATA OUT1
2408
2)
Constant speed
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...