76 Modbus/TCP – Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal) –> READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal) –> OPERATING (Speed mode).
Starting up fieldbus communication for ACS880
and ACS580 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by selecting the correct slot number in parameter
50.01 FBA A enable.
The selection must correspond to the slot where the adapter
module is installed. For example, if the adapter module is
installed in slot 1, you must select slot 1.
3. With parameter 50.02 FBA A comm loss func, select how the
drive reacts to a fieldbus communication break.
Note that this function monitors both communication between
the fieldbus master and the adapter module and
communication between the adapter module and the drive.
4. With parameter 50.03 FBA A comm loss t out, define the time
between communication break detection and the selected
action.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...