254 PROFINET IO – Start-up
20
TELEGRAM TYPE
Read-only.
Indicates the telegram type
selected for PROFINET IO communication.
The adapter module automatically detects the
telegram type defined in the PLC.
For more information on the supported PPO
message types, see section
PPO types
on
page
326
.
0
=
Unknown
ACS355:
FB PAR 20
ACSM1:
FBA PAR20
ACS850/ACQ810:
FBA par20
ACS880/ACS580:
Telegram type
0
= Unknown
Cyclical communication between the master
and the module has not been established yet.
1
= PPO1
Not supported
2
= PPO2
Not supported
3
= PPO3
PPO3 selected
4
= PPO4
PPO4 selected
5
= PPO5
Not supported
6
= PPO6
PPO6 selected
7
= PPO7
PPO7 selected. Not supported with ACS355.
8
= ST1
ST1 selected
9
= ST2
ST2 selected. Not supported with ACS355.
21
ALARM DISABLE
Disables PROFINET IO alarms.
For more information on the diagnostics and
alarm mechanism for PROFINET IO, see
section
Diagnostic and alarm mechanism
on
page
351
.
0
=
Enabled
ACS355:
FB PAR 21
ACSM1:
FBA PAR21
ACS850/ACQ810:
FBA par21
ACS880/ACS580:
Alarm disable
0
= Enabled
PROFINET IO alarms are enabled.
1
= Disabled
PROFINET IO alarms are disabled.
No.
Name/Value
Description
Default
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...