EtherNet/IP – Diagnostics 243
MODULE
Off
There is no power applied to the device.
Green
Device is operating in a normal condition.
Flashing green
Device needs commissioning due to
configuration missing, incomplete or
incorrect. The device may be in the
Standby state. This may be caused by
the adapter waiting for a response from a
DHCP server or Duplicate Address
Detection to complete.
Flashing red
Ethernet interface is disabled. Duplicate
Address Detection may have detected a
duplicate address. Check the IP
configuration and either initiate a
Fieldbus Adapter parameter refresh or
cycle power to the drive.
Flashing red-
green
Device is in Self Test.
Flashing orange,
alternating with
the HOST
Flashing orange
Internal file system error. The error may
be cleared by cycling drive power. If the
error persists, contact your local ABB
representative.
Name
Color
Function
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...