EtherNet/IP – Start-up 147
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for ACS880
/ACS580 drives
Description
50.01 FBA A enable
1
= Option slot 1
2)
Enables communication between
the drive and the fieldbus adapter
module.
50.02 FBA A comm loss
func
1
= Fault
2)
Enables fieldbus A
communication fault monitoring.
50.03 FBA A comm loss t
out
3.0 s
2)
Defines the fieldbus A
communication break supervision
time.
50.04 FBA A ref1 type
4
= Speed
Selects the fieldbus A reference 1
type and scaling.
51.01 FBA A type
128
= ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 Protocol/Profile
100
= EIP AC/DC
Selects the EtherNet/IP protocol
and the ODVA AC/DC drive
profile.
51.03 Commrate
0
= Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 IP configuration
0
= Static IP
2)
Configuration will be obtained
from configuration parameters
05
…
13
.
51.05 IP address 1
192
2)
First part of the IP address
51.06 IP address 2
168
2)
Second part of the IP address
51.07 IP address 3
0
2)
Third part of the IP address
51.08 IP address 4
16
2)
Last part of the IP address
51.09 Subnet CIDR
24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
51.23 ODVA speed scale
128
2)
Sets the scaling for the ODVA
speed reference.
52.01 FBA data in1
01.14
2)
Output power
52.03 FBA data in3
01.11
2)
DC voltage
53.01 FBA data out1
22.26
2)
Constant speed 1
53.03 FBA data out3
22.27
2)
Constant speed 2
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...